The following is the Retrofit Section of the Uniform Code of Building Conservation. It was written by a team of structural engineers who are the leading experts in the field of seismic retrofit. They volunteered their time and expertise to develop this building code for the safety of the general public. Unfortunately no Bay Area cities have adopted this code and only the city of San Leandro has adopted any retrofit code at all. See our webpage entitled False Security. We can expect all Bay Area cities to adopt a retrofit code AFTER the next big earthquake...as Los Angeles did immediately after the Northridge earthquake killed 57 people and caused $20 billion in damage. Many of the drawings and tables referred to in the following text have been left out of this website for the sake of space.
Complete copies of this code are available from the International Conference of Building Officials at
SECTION A601 - GENERAL A601.1 Purpose. The provisions of this chapter are intended to promote public safety and welfare by reducing the risk of earthquake induced damage to existing wood-framed residential buildings. The requirements contained in this chapter are prescriptive minimum standards intended to improve the seismic performance of residential buildings, but will not necessarily prevent earthquake damage. This chapter sets standards for strengthening that may be approved by the building official without requiring plans or calculations prepared by an architect or an engineer. The provisions of this chapter are not intended to prevent the use of any material or method of construction not prescribed herein. The building official may require that construction documents for strengthening using alternate material or methods be prepared by an architect or engineer. A601.2 Scope. The provisions of this chapter apply to light, wood-frame Group R, Division 3 and Group R, Division 1 Occupancies located in Seismic Zones 3 and 4, containing one or more of the structural weaknesses specified in Section A603.
The provisions of this chapter do not apply to structures, or portions thereof, constructed on a concrete slab on grade. The details and prescriptive provisions herein are not intended to be the only acceptable strengthening methods permitted. Alternate details and methods may be used when approved by the building official. Approval of alternates shall be based on test data showing that the method or material used is at least equivalent in terms of strength, deflection and capacity as provided by the prescriptive methods and materials. See Table A-6-C for the capacities provided by the prescriptive elements and connections. The provisions of this chapter may be used to strengthen historic structures provided they are not in conflict with other related provisions and requirements that may apply. A601.3 Alternative Design Procedures. When analysis by an engineer or architect is required in accordance with Section A601.2, such analysis shall be in accordance with all requirementsof the Building Code, except that the base shear may be determined in accordance with the following: V = 0.33ZW (A1-1) SECTION A602 - DEFINITIONS For the purpose of this chapter, in addition to the applicable definitions in the Building Code, certain additional terms are defined as follows: CHEMICAL ANCHOR is an assembly consisting of a threaded rod, washer, nut and chemical adhesive approved by the building official for installation in existing concrete or masonry. COMPOSITE PANEL is a wood structural panel product composed of a combination of wood veneer and wood-based material and bonded with waterproof adhesive. CRIPPLE WALL is a wood-framed stud wall extending from the top of the foundation to the underside of the lowest floor framing. EXPANSION BOLT is a single assembly approved by the building official for installation in existing concrete or masonry.For the purpose of this chapter, expansion bolts shall contain a base designed to expand when properly set, wedging the bolt in the predrilled hole. Assembly shall also include appropriate washer and nut. ORIENTED STRAND BOARD (OSB) is a mat-formed wood structural panel product composed of thin rectangular wood strands or wafers arranged in oriented layers. PERIMETER FOUNDATION is a foundation system that is located under the exterior walls of a building. PLYWOOD is a wood structural panel product composed of sheets of wood veneer bonded together with the grain of adjacent layers oriented at right angles to one another. SNUG-TIGHT is as tight as an individual can torque a nut on a bolt by hand using a wrench with a 10-inch (254 mm) long handle and the point at which the full surface of the plate washer is contacting the wood member and slightly indents the wood surface. WAFERBOARD is a mat-formed wood structural panel product composed of thin rectangular wood wafers arranged in random layers and bonded with waterproof adhesive. WOOD STRUCTURAL PANEL is a structural panel product composed primarily of wood and meeting the requirements of United States Voluntary Product Standard PS 1 and United States Voluntary Product Standard PS 2. Wood structural panels include all-veneer plywood, composite panels containing a combination of veneer and wood-based material, and mat-formed panels such as oriented strand board and waferboard.
SECTION A603 - STRUCTURAL WEAKNESSES For the purpose of this chapter, structural weaknesses shall be as specified below. 1. Sill plates or floor framing that are supported directly on the ground without an approved foundation system. 2. A perimeter foundation system that is constructed only of wood posts supported on isolated pad footings. 3. Perimeter foundation systems that are not continuous.
4. A perimeter foundation system that is constructed of unreinforced masonry. 5. Sill plates that are not connected to the foundation or are connected with less than what is required by the Building Code.
6. Cripple walls that are not braced in accordance with the requirements of Section A604.4 and Table A-6-A or cripple walls not braced with diagonal sheathing or wood structural panels in accordance with the Building Code. SECTION A604 - STRENGTHENING REQUIREMENTS A604.1 General. A604.1.1 Scope. The structural weaknesses noted in Section A603 shall be strengthened in accordance with the requirements of this section. Strengthening work may include both new construction and alteration of existing construction. Except as provided herein, all strengthening work and materials shall comply with the applicable provisions of the Building Code. Alternate methods of strengthening may be used provided such systems are designed by an engineer or architect and approved by the building official. A604.1.2 Condition of existing wood materials. All existing wood materials that will be a part of the strengthening work (sills, studs, sheathing, etc.) shall be in a sound condition and free from defects that substantially reduce the capacity of the member. Any wood material found to contain fungus infection shall be removed and replaced with new material. Any wood material found to be infested with insects or to have been infested with insects shall be strengthened or replaced with new materials to provide a net dimension of sound wood at least equal to its undamaged original dimension. A604.1.3 Floor joists not parallel to foundations. Floor joists framed perpendicular or at an angle to perimeter foundations shall be restrained by either an existing nominal 2-inch (51 mm) wide continuous rim joist or by nominal 2-inch (51 mm) wide full depth blocking between alternate joists in one- and two-story buildings, and between each joist in three-story buildings. Existing blocking for multistory buildings must occur at each joist space above a braced cripple wall panel. Existing connections at the top and bottom edge of an existing rim joist or blocking need not be verified in one-story buildings. In multistory buildings the existing top edge connection need not be verified; however, bottom edge connection to either the foundation sill plate or top plate of a cripple wall shall be verified. The minimum existing bottom edge connection shall consist of 8d toe nails spaced 6 inches (152 mm) apart for a continuous rim joist or three 8d toenails per block. When this minimum bottom edge connection is not present, or cannot be verified, a supplemental connection installed as shown in Figure A-6-8 shall be provided. Where an existing continuous rim joist or the minimum existing blocking does not occur, new 3/4-inch (19 mm) wood structural panel blocking installed tightly between floor joists and nailed as shown in Figure A-6-8 shall be provided at the inside face of the cripple wall and nailed as shown in Figure A-6-8. In lieu of 3/4-inch (19 mm) wood structural panel blocking, tightfitting, full depth 2 (51 mm) blocking, may be used. New blocking may be omitted where it will interfere with vents or plumbing that penetrates the wall. A604.1.4 Floor joists parallel to foundations. Where existing floor joists are parallel to the perimeter foundations, the end joist shall be located over the foundation and, except for required ventilation openings, shall be continuous and in continuous contact with the foundation sill plate or top plate of the cripple wall. Existing connections at the top and bottom edge of the end joist need not be verified in one-story buildings. In multistory buildings, the existing top edge connection of the end joist need not be verified; however, the bottom edge connection to either the foundation sill plate or the top plate of a cripple wall shall be verified. The minimum bottom edge connection shall be 8d toenails spaced 6 inches (152 mm) apart. If this minimum bottom edge connection is not present, or cannot be verified, a supplemental connection installed as shown in Figure A-6-9 shall be provided. A604.2 Foundations. A604.2.1 New perimeter foundations. New perimeter foundations shall be provided for structures with the structural weaknesses noted in Items 1 and 2 of Section A603. Soil investigations or geotechnical studies are not required for this work unless the building is located in a special study zone as designated by the jurisdiction or other public agency. A604.2.2 Foundation evaluation by engineer or architect. Partial perimeter foundations or unreinforced masonry foundations shall be evaluated by an engineer or architect for the force levels noted in Formula (A1-1). Test reports or other substantiating data to determine existing foundation material strengths shall be submitted for review. When approved by the building official, these foundation systems may be strengthened in accordance with the recommendations included with the evaluation in lieu of being replaced.
A604.2.3 Details for new perimeter foundations. All new perimeter foundations shall be continuous and constructed according to one of the details shown in Figure A-6-1 or A-6-2.
A604.2.4 Required compressive strength. New concrete foundations shall have a minimum compressive strength of 2,500 psi (17.24 MPa) at 28 days. A604.2.5 New hollow-unit masonry foundations. New hollowunit masonry foundations shall be solidly grouted. Mortar shall be Type M or S, and the grout and masonry units shall comply with the Building Code. A604.2.6 Reinforcing steel. Reinforcing steel shall comply with the requirements of the Building Code. A604.3 Foundation Sill Plate Anchorage. A604.3.1 Existing perimeter foundations. When the building has an existing continuous perimeter foundation, all perimeter wall sill plates shall be bolted to the foundation with chemical anchors or expansion bolts in accordance with Table A-6-A. Anchors or bolts shall be installed in accordance with Figure A-6-3 with the plate washer installed between the nut and the sill plate. The nut shall be tightened to a snug-tight condition after curing is complete for chemical anchors and after expansion wedge engagement for expansion bolts. The installation of nuts on all bolts shall be subject to verification by the building official. Where existing conditions prevent anchor or bolt installation through the sill plate, this connection may be made in accordance with Figure A-6-4A, A-6-4B or A-6-4C. The spacing of these alternate connections shall comply with the maximum spacing requirements of Table A-6-A. Expansion bolts shall not be used when the installation causes surface cracking of the foundation wall at the location of the bolt. A604.3.2 Placement of chemical anchors and expansion bolts. Chemical anchors or expansion bolts shall be placed within 12 inches (305 mm), but not less than 9 inches (229 mm), from the ends of sill plates and shall be placed in the center of the stud space closest to the required spacing. New sill plates may be installed in pieces when necessary because of existing conditions.For lengths of sill plate greater than 12 feet (3658 mm), anchors or bolts shall be spaced along the sill plate as noted in Table A-6-A.For other lengths of sill plate, see Table A-6-B. For lengths of sill plates less than 30 inches (762 mm), a minimum of one anchor or bolt shall be installed.
A604.3.3 New perimeter foundations. Sill plates for new perimeter foundations shall be bolted as required by Table A-6-A and as shown in Figure A-6-1 or A-6-2. A604.4 Cripple Wall Bracing. A604.4.1 General. Exterior cripple walls, not exceeding 4 feet (1219 mm) in height, shall use the prescriptive bracing method listed below. Cripple walls over 4 feet (1219 mm) in height require analysis by an engineer or architect in accordance with Section A601.3. A604.4.1.1 Sheathing installation requirements. Wood structural panel sheathing shall not be less than 15/32-inch (12 mm) thick and installed in accordance with either Figure A-6-5 or A-6-6. All individual pieces of wood structural panels shall be nailed with 8d common nails spaced 4 inches (102 mm) on center at all edges and at 12 inches (305 mm) on center at each intermediate support with not less than two nails for each stud. Nails shall be driven so that their heads on crowns are flush with the surface of the sheathing and shall penetrate the supporting member a minimum of 11/2 inches (38 mm). When a nail fractures the surface, it shall be left in place and not counted as part of the required nailing. A new 8d nail shall be located within 2 inches (51 mm) of the discounted nail and hand driven flush with the sheathing surface. All horizontal joints must occur over nominal 2-inch-by-4-inch (51 mm by 102 mm) blocking installed with the nominal 4-inch (102 mm) dimension against the face of the plywood. Vertical joints at adjoining pieces of wood structural panels shall be centered on existing studs such that there is a minimum 1/8 inch (3.2 mm) between the panels and the nails are placed a minimum of 1/2 inch (12.7 mm) from the edges of the existing stud. Where such edge distances cannot be maintained because of the width of the existing stud, a new stud shall be added adjacent to the existing studs and connected in accordance with Figure A-6-7. 604.4.2 Distribution and amount of bracing. See Table A-6-A and Figure A-6-10 for the distribution and amount of bracing required. Each braced panel must be at least two times the height of the cripple stud wall but not less than 48 inches (1219 mm) in length or width. Where the minimum amount of bracing prescribed in Table A-6-A cannot be installed along any walls, the bracing must be designed in accordance with Section A601.3.
A604.4.3 Stud space ventilation. When bracing materials are installed on the interior face of studs forming an enclosed space between the new bracing and existing exterior finish, each braced stud space must be ventilated. Adequate ventilation and access for future inspection shall be provided by drilling one 2-inch to 3-inch (51 mm to 76 mm) diameter round hole through the sheathing nearly centered between each stud at the top and bottom of the cripple wall. Such holes should be spaced a minimum of 1-inch (25 mm) clear from the sill or top plates. In stud spaces containing sill bolts, the hole shall be located on the center line of the sill bolt but not closer than 1-inch (25 mm) clear from the nailing edge of the sheathing. When existing blocking occurs within the stud space, additional ventilation holes shall be placed above and below the blocking or the existing block shall be removed and a new nominal 2-inch by 4-inch (51 mm by 102 mm) block installed with the nominal 4-inch (102 mm) dimension against the face of the plywood. For stud heights less than 18 inches (457 mm), only one ventilation hole will be provided. A604.4.4 Existing underfloor ventilation. Existing underfloor ventilation shall not be reduced without providing equivalent new ventilation as close to the existing as possible. Braced panels may include underfloor ventilation openings when the height of the opening, measured from the top of the foundation wall to the top of the opening, does not exceed 25 percent of the height of the cripple stud wall; however, the length of the panel shall be increased a distance equal to the length of the opening or one stud space minimum. Where an opening exceeds 25 percent of the cripple wall height, braced panels shall not be located where the opening occurs. See Figure A-6-7.
A604.5 Quality Control. All work shall be subject to inspection by the building official including, but not limited to: 1. Placement and installation of new chemical anchors or expansion bolts installed in existing foundations. Special inspection is not required for chemical anchors installed in existing foundations regulated by the presecriptive provisions of this chapter. 2. Installation and nailing of new cripple wall bracing. 3. Any work may be subject to special inspection when required by the building official in accordance with the Building Code. A604.6 Phasing of the Strengthening Work. When approved by the building official, the strengthening work contained in this chapter may be completed in phases. The strengthening work in any phase shall be performed on two parallel sides of the structure at the same time. |
|
|
|